Exhaust Fan Grease Containment

NFPA 96 Fire Codes for Rooftop Grease Containment

7.8.2 Rooftop terminations

7.8.2.1 Rooftop termination shall be arranged with or provided with the following:

(4) The ability to drain grease out of any traps or low points formed in the fan or duct near the termination of the system into a collection container that is noncombustible, closed, rainproof, and structurally sound for the service to which it is applied and that will not sustain combustion.

(5) A grease collection device that is applied to exhaust systems that do not inhibit the performance of any fan.

[6] Listed grease collection systems that meet the requirements of 7.8.2.1(4) and 7.8.2.1(5)

8.1 Exhaust Fans for Commercial Cooking Equipment.

8.1.1.3 Upblast fans shall have a drain directed to a readily accessible and visible grease receptacle not to exceed 3.8 L (1 gal).

Contact us!

Sparkle My Hood-uses proven methods for removing grease and flammable residues from the interior surfaces of the kitchen hood canopies, filters, ductwork and exhaust fans. We ensure compliance with fire and health codes. We hand/steam clean the entire kitchen exhaust hood and duct system from top to bottom. Kitchen Exhaust Hood system: fan, duct, filters, to bare metal in accordance with NFPA 96 Code Standards for Ventilation Control and Fire Protection